Fast Response
09.00 AM - 05.00 PM , Email : sales@tokobest.com
get in touch -

Kyoritsu KEW 4105DL-H Earth Tester

Kyoritsu KEW 4105DL-H Earth Tester

Kyoritsu KEW 4105DL-H Earth Tester

  • Brand : Kyoritsu
  • Product Code : KEW 4105DL-H
  • Availability : In Stock
  • Rp5,500,000,-

  • Ex Tax:Rp5,500,000,-

Kyoritsu Indonesia - Kyoritsu KEW 4105DL-H Earth Tester

Hard Case Model

• 3pole and 2pole Earth Resistance measurement (0.01Ω-2000Ω)
• Waterproof design (IP67)
• Rotary Switch makes the user interface very intuitive
• Large LCD Display with Backlight
• Led to monitor correct / non correct auxiliary earth spike resistance
• Earth Voltage Measurement (AC/DC 0-300V)
• CAT Ⅳ 100V

Earth resistance
measurement20Ω200Ω2000Ω
Measuring range 0.00 - 2000 Ω Display range 0.00 - 20.99 Ω 0.0 - 209.9 Ω 0 - 2099 Ω Accuracy*1 ±1.5%rdg±0.08 Ω*2 ±1.5%rdg±4dgt Auxiliary earth resistance*3 <10kΩ  <50kΩ  <100kΩ Comparator reference value 10Ω  100Ω  500Ω Earth voltage measurement
Measuring range 0 - 300 V AC (45 - 65Hz) ±0 - ±300 V DC Display range 0.0 - 314.9 V 0.0 - ±314.9 V Accuracy ±1%rdg±4dgt Overload protection Earth resistance : 360V AC (10 seconds) Earth voltage : 360V AC (10 seconds) Applicable Standards IEC 61010-1, CAT IV 100 V /CAT III 150 V /CAT II 300 V Pollution degree 3 IEC 61010-2-030,IEC 61010-031, IEC 61557-1, -5 IEC 60529 IP67, IEC 61326-1, -2-2, EN50581(RoHS) Power source LR6(AA)(1.5V) × 6 Dimensions 121(L) × 188(W) × 59(H) mm (including case lid) Weight Approx. 690g (including batteries and case lid) Accessories
for 4105DL  7127B(Simplified measurement probe) 8041(Auxiliary earth spikes[2 spikes/1set]) 9121(Shoulder strap) 7267(Cable reel for Earth resistance tester (red)) 7268(Cable reel for Earth resistance tester (yellow)) 7271(Earth resistance test leads) 9190(Carrying case) LR6(AA) × 6, Instruction manual Accessories
for 4105DL-H 7127B(Simplified measurement probe) 8041(Auxiliary earth spikes[2 spikes/1set]) 9121(Shoulder strap)  7266(Earth resistance test leads[red-20m, yellow-10m, green-5m/1set]) 9191(Hard case) LR6(AA) × 6, Instruction manual Optional 7272(Precision measurement Cord set) 8259(Adapter for measurement terminal)

*1 For precision measurement, auxiliary earth resistance should be 100 Ω ±5% or less.
*2 At simplified measurement add ±0.10 Ω to the specified accuracy.
*3 Accuracy within the auxiliary earth resistance: ±5% rdg ±10 dgt.